What this calculator does
Attic ventilation is sized by net free area (NFA), the open area that actually lets air through. A common rule is one unit of NFA for every 300 units of attic floor area, with a tighter 1/150 ratio in cold climates or where a vapor barrier is limited, and a looser 1/600 ratio in some code allowances. The vent area should be balanced between low intake at the soffits and high exhaust at the ridge or gables. This calculator converts the floor area and ratio into NFA, then splits it. It does not choose a vent product; vent manufacturers publish NFA per piece, and the nominal opening is usually larger than the net area.
How to use it
- Measure the attic floor length and width, not the roof slope area.
- Choose the vent ratio that matches your climate and code.
- Set the intake share; 50–60% low intake is a common balanced design.
- Read the total NFA and the intake and exhaust areas.
- Convert to vent pieces using each product's published NFA rating.
How it works
Example calculations
Example 1: 10 × 8 m attic at 1/300
The floor area is 80.0 m². At 1/300 the required NFA is 0.267 m², or 2,667 cm². A 50/50 split gives 1,333 cm² of intake and the same amount of exhaust.
Example 2: 12 × 10 m attic at 1/150
The tighter ratio doubles the requirement: 120.0 m² ÷ 150 = 0.80 m², or 8,000 cm². At a 50% intake share, each side needs 4,000 cm² of net free area.
Example 3: 15 × 9 m attic at 1/600, 60% intake
The 1/600 allowance reduces the total to 0.225 m², or 2,250 cm². A 60% intake share puts 1,350 cm² low and 900 cm² high. The looser ratio is only valid where the code and the vapor barrier allow it.
What the result means
The ratio is a minimum, not a target for arbitrary vent placement. A large exhaust vent with no low intake can pull air from the house instead of the soffits, which wastes energy and can worsen moisture. Soffit vents must be open, not blocked by insulation, and ridge vents need a clear slot. The NFA printed on a vent is the number to use; a 300 mm × 300 mm louver with 50% free area provides 0.045 m² of NFA, not 0.09 m². Local codes, shingle warranties, and climate affect the right ratio. In cold climates, air sealing and insulation usually matter more than adding vents.
Common mistakes
- Using the roof area instead of the attic floor area.
- Using the vent's nominal size instead of its net free area.
- Installing all exhaust and no low intake.
- Blocking soffit vents with insulation or storing boxes against them.
- Applying a 1/600 allowance where the code or vapor barrier requires 1/150.
Assumptions and limits
- The attic floor is rectangular and fully ventilated.
- The vent ratio is the code or manufacturer minimum for the climate.
- Net free area is measured after screens, louvers, and framing.
- Intake and exhaust are both unobstructed.
- No mechanical ventilation or air-conditioned attic is included.
Frequently asked questions
What is net free area?
Net free area is the actual open area of a vent after subtracting the screen, louvers, and frame. It is always smaller than the nominal opening. Use the manufacturer's NFA rating, not the outside dimensions.
Which ratio should I use?
1/300 is a common minimum. 1/150 is used in colder climates or where a vapor barrier is limited; 1/600 appears in some code allowances with a proper vapor barrier. Follow the local code and the shingle manufacturer's requirements.
How do I split intake and exhaust?
A balanced design uses roughly equal NFA low and high, and many builders use 50–60% intake. The exact split depends on the roof design and the vent products. The key is a continuous low intake path and a high exhaust path.
Can I have too much ventilation?
More is not automatically better if it is unbalanced or if it bypasses insulation. Excessive exhaust without intake can depressurize the attic. Design the intake and exhaust together and air-seal the ceiling first.
Do ridge vents count as exhaust?
Yes, ridge vents are a common high exhaust. They need a clear opening at the ridge and should be paired with soffit intake. Some ridge vents perform poorly if the roof deck is not cut back properly.
Does this apply to a conditioned attic?
No. A conditioned or encapsulated attic is inside the building envelope and is insulated at the roof line. It needs a different design, often with no attic ventilation. Consult a building scientist or contractor.
Sources
2026 update
How to use the professional output
This page is not just a formula box. The result is designed to be checked, compared, and taken away.
- Professional worksheet. The result includes the inputs used, the method and scope, and a one-variable sensitivity check for finance calculators.
- A/B scenarios. Save two input sets in the browser and compare the primary, secondary, and breakdown figures side by side.
- Print / PDF and CSV. Print a branded worksheet, or export the year-by-year table when the calculator produces one.
The formulas and assumptions above still govern the number. The worksheet makes the estimate auditable; it does not make it a lender quote, tax return, or personalized advice.