What this calculator does
Duct size is a balance between airflow, velocity, and pressure loss. A duct that is too small makes the fan work harder, raises noise, and can starve distant rooms; a duct that is too large costs more, takes up space, and can reduce the velocity needed to carry air properly. The basic relationship is simple: cross-sectional area equals airflow divided by velocity. The practical work is choosing a velocity that suits the application, then translating the area into a standard round or rectangular size. This calculator does that translation and shows the equivalent round and rectangular dimensions. It is a starting point for a manual J/S or a contractor's design, not a substitute for one. Fittings, length, bends, insulation, and the available static pressure all affect the final size.
How to use it
- Enter the design airflow for the branch or trunk in cubic metres per hour.
- Enter a target velocity; supply branches often run at 3 to 6 m/s.
- Choose round or rectangular duct.
- For rectangular duct, set a width-to-height ratio that fits the space.
- Check the cross-section and the equivalent size in the other shape.
- Confirm the result with a full duct design that accounts for fittings and pressure loss.
How it works
Example calculations
Example 1: 600 m3/h at 5 m/s
The cross-section is 333 cm2. A round duct needs a diameter of 206 mm. The rectangular equivalent at a 2.0:1 ratio is 258 x 129 mm. The round and rectangular shapes carry the same area but have different perimeter and friction characteristics.
Example 2: A larger rectangular trunk
At 1,200 m3/h and 6.0 m/s, the area is 556 cm2. With a 2.5:1 ratio the rectangular duct is 373 x 149 mm. The equivalent round diameter is 266 mm, which may be harder to fit above a ceiling than the flatter rectangular shape.
Example 3: A small branch at low velocity
A 300 m3/h branch at 3.0 m/s needs 278 cm2 and a 188 mm round duct. Lower velocity reduces noise but requires a larger duct for the same airflow. The right balance depends on the room, the run length, and the fan's available pressure.
What the result means
The area calculation is exact, but the velocity choice is a design decision. A higher velocity shrinks the duct and saves space, at the cost of more noise and pressure loss. A lower velocity is quieter but needs more room. In the default case a 206 mm round duct is a common branch size for a few hundred cubic metres per hour. The rectangular equivalent is wider but flatter, which helps in a ceiling void. The sizes shown are theoretical: standard duct fittings come in fixed increments, and the actual design must account for the equivalent length of bends, transitions, and grilles.
Common mistakes
- Using the fan's free-air airflow instead of the design airflow at the required static pressure.
- Choosing a velocity that is too high and creating noise or excessive pressure drop.
- Sizing a long run with many bends using only the straight-duct area.
- Ignoring the space available for insulation and fittings.
- Mixing up cubic metres per hour with litres per second.
- Treating the result as a code-compliant design rather than a starting point.
Assumptions and limits
- The airflow entered is the design airflow for the section being sized.
- The target velocity is appropriate for the application and noise goal.
- The duct is straight and the pressure loss is dominated by the cross-section.
- The aspect ratio is a practical fit for the available space.
- Fittings, insulation, and system effects are not included in the size.
- The result is a sizing aid, not a full HVAC design.
Frequently asked questions
What velocity should I use for a supply duct?
Many residential supply branches are designed around 3 to 6 m/s, with lower velocities near occupied rooms to control noise. Main trunks can run higher if the pressure budget allows. The right value depends on the system and the noise criteria, so confirm it with the equipment and the room layout.
How do I convert m3/h to m3/s?
Divide by 3,600. The calculator does this internally. For example, 600 m3/h is 0.1667 m3/s. Mixing the units is a common source of sizing errors, so check the field labels before entering a number.
Is a round or rectangular duct better?
Round duct has less perimeter and lower friction for the same area, so it is efficient. Rectangular duct fits into shallow ceiling voids and is easier to route in some buildings. The choice is usually a compromise between space, pressure loss, and cost.
How does the aspect ratio affect the duct?
A higher aspect ratio makes the duct wider and flatter for the same area. That can fit a shallow ceiling, but it increases the perimeter and friction, and very flat ducts can be noisy. A ratio around 2:1 is a common compromise; the calculator accepts 1:1 to 4:1.
Does this calculator account for friction loss?
No. It sizes the duct from continuity, area equals flow divided by velocity. A full design uses a friction chart or software to account for length, fittings, and pressure drop. Use this result as a starting size, then check it against the system's available static pressure.
Can I use this for exhaust duct?
The same area relationship applies, but exhaust systems have different velocity and pressure requirements, and grease or moisture may call for specific materials. Confirm the design with the appliance manufacturer and local code before installing.
Sources
2026 update
How to use the professional output
This page is not just a formula box. The result is designed to be checked, compared, and taken away.
- Professional worksheet. The result includes the inputs used, the method and scope, and a one-variable sensitivity check for finance calculators.
- A/B scenarios. Save two input sets in the browser and compare the primary, secondary, and breakdown figures side by side.
- Print / PDF and CSV. Print a branded worksheet, or export the year-by-year table when the calculator produces one.
The formulas and assumptions above still govern the number. The worksheet makes the estimate auditable; it does not make it a lender quote, tax return, or personalized advice.