What this calculator does
Thermal resistance measures how well a layer of insulation resists heat flow. In metric units it is RSI, in square metres kelvin per watt; in imperial units it is R-value, in square feet Fahrenheit hours per Btu. The two are proportional, and both are inversely related to the U-value, which describes heat flow per square metre per degree of temperature difference. Because insulation performance depends on thickness and conductivity, the same material can meet very different targets depending on how much is installed. This calculator converts between the measures and shows the thickness needed to reach a chosen target, which is useful when comparing products or checking a specification.
How to use it
- Enter the installed insulation thickness in millimetres.
- Enter the thermal conductivity from the product data sheet.
- Set a target RSI if you want to find the required thickness.
- Enter a temperature difference for the heat-flow estimate.
- Compare RSI, R-value, and U-value across products.
How it works
Example calculations
Example 1: 100 mm of mineral wool at 0.035 W/m·K
The layer has RSI 2.86 and an imperial R-value of about 16.2. The U-value is 0.350 W/m²K, so a 20 °C difference drives about 7.0 W/m² through the insulation alone.
Example 2: 200 mm of a high-performance board at 0.022 W/m·K
Doubling the thickness and lowering the conductivity raises RSI to 9.09 and the imperial R-value to about 51.6. Reaching a target of 6.0 RSI needs about 132 mm of this material.
Example 3: 50 mm of a lower-performance material at 0.040 W/m·K
A thinner, more conductive layer gives only RSI 1.25 and R-value 7.1. To reach 2.0 RSI with this material would take about 80 mm.
What the result means
The calculation covers the insulation layer only. In a real wall or roof, surface resistances, timber or steel framing that bridges the insulation, air gaps, and moisture reduce the whole-assembly performance, often substantially. The U-value shown is therefore a best-case figure for the insulation itself, not the U-value of the completed element. Building codes set target R-values by climate zone and building element, and the right target depends on where you build and how the assembly is constructed. Use the calculator to compare products and check thickness, then confirm the assembly performance with a qualified designer.
Common mistakes
- Comparing RSI and imperial R-values without converting.
- Using the insulation R-value as the whole-wall R-value.
- Ignoring thermal bridging through framing.
- Assuming a product's conductivity is constant across temperatures.
- Choosing thickness without checking the code target for the climate.
Assumptions and limits
- The insulation layer is continuous and free of gaps.
- Conductivity is constant across the temperature range.
- Moisture and ageing do not change performance.
- Framing, fixings, and surface resistances are excluded.
- The target RSI is a design preference, not a code determination.
Frequently asked questions
What is the difference between RSI and R-value?
Both measure thermal resistance. RSI is the metric unit, m²K/W; R-value is the imperial unit, ft²·°F·h/Btu. One RSI equals about 5.678 units of imperial R-value, so the numbers are not interchangeable without conversion.
What is a U-value?
The U-value is the reciprocal of thermal resistance and describes heat flow per square metre per degree of temperature difference. A lower U-value means better insulation. It is usually quoted for a complete assembly, not just the insulation layer.
Why is my wall's R-value lower than the insulation's?
Framing, screws, and other penetrations bridge the insulation and conduct heat, and surface films add resistance. The whole-assembly R-value is therefore lower than the nominal insulation value, sometimes by 15 to 25 percent or more.
Does thickness alone determine performance?
No. Performance also depends on conductivity, installation quality, moisture, and ageing. A thicker lower-performance product can underperform a thinner high-performance one.
How do I find the target R-value?
Check the building code for your climate zone and the element being insulated. Codes commonly set minimum R-values for roofs, walls, and floors, and the targets differ significantly between cold and mild climates.
Can I use this for a multi-layer assembly?
Yes, by adding the RSI of each continuous layer. The calculator handles one layer at a time; sum the results for a multi-layer build-up, and account separately for bridging and surface resistances.
Sources
2026 update
How to use the professional output
This page is not just a formula box. The result is designed to be checked, compared, and taken away.
- Professional worksheet. The result includes the inputs used, the method and scope, and a one-variable sensitivity check for finance calculators.
- A/B scenarios. Save two input sets in the browser and compare the primary, secondary, and breakdown figures side by side.
- Print / PDF and CSV. Print a branded worksheet, or export the year-by-year table when the calculator produces one.
The formulas and assumptions above still govern the number. The worksheet makes the estimate auditable; it does not make it a lender quote, tax return, or personalized advice.