What this calculator does
An off-grid solar battery bank has to carry the house through cloudy days, not just one night. The sizing calculation starts with daily energy use, multiplies by the number of autonomy days, and divides by the usable depth of discharge and the inverter efficiency. That gives the required bank energy before rounding to real batteries. The next step is the series and parallel arrangement: a 48 V system built from 12 V batteries needs four in series per string, and the number of strings depends on the required amp-hours and the capacity of each battery. This calculator does both steps and shows the installed capacity after rounding. It is a first-pass sizing tool; ageing, temperature, peak load, and charge-controller losses still need to be checked.
How to use it
- Add up daily energy use in kWh from appliances and lighting.
- Choose the number of days the bank should carry the load without sun.
- Enter the planned depth of discharge, leaving margin for battery life.
- Enter the inverter efficiency from its datasheet.
- Choose the system voltage and the voltage and capacity of each battery.
- Round up to whole batteries and check the peak load against the bank's discharge capability.
How it works
Example calculations
Example 1: 10 kWh/day for two days
A 10 kWh daily load with 2 days of autonomy, 80% depth of discharge, and 90% inverter efficiency needs 10 × 2 / (0.8 × 0.9) = 27.8 kWh. At 48 V that is 579 Ah. Using 12 V 100 Ah batteries, four go in series per string and six strings are needed, for 24 batteries and 28.8 kWh installed.
Example 2: A small 24 V cabin system
A 5 kWh daily load for 1 day at 70% depth and 85% efficiency needs 8.4 kWh, or 350 Ah at 24 V. With 12 V 200 Ah batteries, two in series per string and two strings give 4 batteries and 9.6 kWh installed. The extra capacity covers the rounding and gives a little margin.
Example 3: A larger 48 V bank
A 20 kWh daily load for 3 days at 90% depth and 95% efficiency needs 70.2 kWh, or 1,462 Ah at 48 V. Using 48 V 100 Ah batteries, one battery per string and 15 strings give 15 batteries and 72.0 kWh installed. The bank is large, so peak discharge current and ventilation need checking as well.
What the result means
The required kWh is the energy the bank must store before rounding. The installed kWh is what the actual battery count provides, which is usually a little higher. The series and parallel lines tell you how the bank is wired: series raises voltage, parallel raises capacity. The depth of discharge is a trade-off between usable capacity and battery life; a lower depth means a larger, more expensive bank for the same load. The estimate excludes temperature derating, ageing, and peak current limits, so check the battery datasheet and the inverter's surge requirement before ordering.
Common mistakes
- Sizing for one night instead of the intended autonomy period.
- Using the battery's full capacity without accounting for depth of discharge.
- Forgetting inverter and wiring losses.
- Mixing battery voltages in a series string.
- Ignoring the peak discharge current and the inverter surge rating.
- Assuming the installed kWh is fully usable at end of life.
Assumptions and limits
- Daily energy use is a representative average, not the peak day.
- The autonomy days are full days without meaningful solar input.
- Depth of discharge and inverter efficiency are constant.
- Batteries are new and at a reasonable operating temperature.
- Battery unit voltage divides evenly into the system voltage.
- Ageing, temperature derating, charge-controller losses, and peak load limits are excluded.
Frequently asked questions
How do I size a solar battery bank?
Multiply daily kWh by autonomy days, then divide by the usable depth of discharge and inverter efficiency. That gives the required bank energy. Divide by the system voltage for amp-hours, then round up to whole batteries in a series-parallel arrangement.
What is depth of discharge?
It is the share of a battery's capacity you use before recharging. A 100 Ah battery discharged to 20% remaining has used 80% depth of discharge. Lower depth generally extends battery life but requires a larger bank.
Why does inverter efficiency matter?
The battery stores DC energy, and the inverter converts it to AC with some loss. If the inverter is 90% efficient, the bank must supply more energy than the load uses. The calculator divides by efficiency to account for that.
How many batteries are in a 48 V bank?
It depends on the battery voltage. Four 12 V batteries in series make 48 V; two 24 V batteries in series also make 48 V; one 48 V battery is a single unit per string. The number of parallel strings depends on the required amp-hours.
Can I add batteries later?
It is possible, but mixing old and new batteries can reduce performance and life. Best practice is to size the bank for the planned load and add batteries of the same type, age, and condition if you expand.
Does this calculator include solar panel sizing?
No. It sizes the battery bank only. Panel and charge-controller sizing depend on location, sun hours, seasonal variation, and the array's charging profile, and should be designed together with the bank.
Sources
2026 update
How to use the professional output
This page is not just a formula box. The result is designed to be checked, compared, and taken away.
- Professional worksheet. The result includes the inputs used, the method and scope, and a one-variable sensitivity check for finance calculators.
- A/B scenarios. Save two input sets in the browser and compare the primary, secondary, and breakdown figures side by side.
- Print / PDF and CSV. Print a branded worksheet, or export the year-by-year table when the calculator produces one.
The formulas and assumptions above still govern the number. The worksheet makes the estimate auditable; it does not make it a lender quote, tax return, or personalized advice.