What this calculator does
Battery runtime is not simply capacity divided by load. The battery's amp-hour rating is measured at a specific discharge rate, only part of its capacity should be used to keep it healthy, and an inverter loses some energy on the way to the appliance. A 100 Ah battery at 12 V holds 1,200 Wh, but a 300 W load will not run for four hours on it. This calculator combines capacity, voltage, depth of discharge, load, and inverter efficiency to estimate runtime, and it shows the load current and the runtime at half load. It is a planning estimate for a new or healthy battery. Age, temperature, discharge rate, and wiring losses all reduce the real runtime, so keep a margin and test the setup before relying on it.
How to use it
- Enter the battery's rated capacity in amp-hours.
- Enter the nominal voltage.
- Set the depth of discharge you are willing to use.
- Enter the load power in watts.
- Enter the inverter efficiency, or 100% for a DC load.
- Read the runtime, then test the actual setup before depending on it.
How it works
Example calculations
Example 1: A 300 W load
A 100 Ah 12 V battery used to 80% depth of discharge and a 90% efficient inverter delivers about 864 Wh to the load, so a 300 W appliance runs for about 2.88 hours. If the load run continuously, the battery would be recharged daily.
Example 2: A smaller load
The same battery with a 60 W load runs for about 14.4 hours. Doubling the load halves the runtime, so it is often more efficient to run a smaller load from the battery and use mains power for heavy appliances. Runtime at half of 300 W is 5 h 46 min, which matches the calculation.
Example 3: A deeper discharge
A lithium battery that can be discharged to 100% delivers 1,080 Wh after inverter losses from the same 100 Ah 12 V pack, giving 3.6 hours at 300 W. A lead-acid battery discharged to 50% delivers only 540 Wh and 1.8 hours. The chemistry, not just the amp-hour rating, sets the usable capacity.
What the result means
The runtime estimate is a best case for a healthy battery at a moderate discharge rate. Real capacity falls in cold weather, falls as the battery ages, and falls when the load draws a high current relative to the battery's rating. Inverters are most efficient near their rated load and less efficient when idling or lightly loaded, so a small standby draw can reduce the figure more than expected. The depth of discharge is a trade-off: using more of the battery gives a longer single run but shortens its life, especially for lead-acid. For critical loads, add a margin of 30% to 50% and test the actual runtime under realistic conditions before relying on it.
Common mistakes
- Ignoring depth of discharge and using the full amp-hour rating.
- Forgetting inverter losses.
- Assuming the rated capacity holds at any discharge rate.
- Mixing amp-hours and watt-hours in the same calculation.
- Using a battery's cold-temperature capacity as if it were room temperature.
- Planning to run a critical load to exactly the calculated runtime.
Assumptions and limits
- The battery is new or in good condition.
- Capacity is stated at a discharge rate similar to the actual load.
- Depth of discharge is the share of capacity that will be used.
- Inverter efficiency is constant over the run.
- Load power is constant and the inverter has no standby draw.
- Temperature and wiring losses are not modelled.
Frequently asked questions
What is the difference between Ah and Wh?
Amp-hours measure charge, while watt-hours measure energy. Multiply amp-hours by voltage to get watt-hours. A 100 Ah battery at 12 V holds 1,200 Wh, while the same 100 Ah at 24 V holds 2,400 Wh.
Why use only part of the battery's capacity?
Deep discharges shorten battery life, especially for lead-acid types. Limiting the depth of discharge to about 50% for lead-acid or 80% for many lithium batteries trades a shorter single run for many more cycles over the battery's life.
How much does the inverter lose?
A typical inverter is about 85% to 95% efficient at moderate loads and less efficient at very low loads. Use the manufacturer's efficiency curve if you have it, and add a little margin for standby power.
Does temperature affect runtime?
Yes. Cold reduces usable capacity, especially for lead-acid batteries, so a battery that runs a load for three hours indoors may run for less than two in freezing conditions. Keep batteries in a suitable environment where possible.
Can I run the battery to 0%?
Some lithium batteries allow a full discharge with a reserve, but doing so regularly shortens life. Lead-acid batteries should not be discharged deeply. Follow the manufacturer's depth-of-discharge recommendation.
How do I estimate runtime for several loads?
Add the wattages of everything that runs at the same time to get the total load, then divide the delivered energy by that total. For loads that cycle on and off, use the average power over the period rather than the peak.
Sources
2026 update
How to use the professional output
This page is not just a formula box. The result is designed to be checked, compared, and taken away.
- Professional worksheet. The result includes the inputs used, the method and scope, and a one-variable sensitivity check for finance calculators.
- A/B scenarios. Save two input sets in the browser and compare the primary, secondary, and breakdown figures side by side.
- Print / PDF and CSV. Print a branded worksheet, or export the year-by-year table when the calculator produces one.
The formulas and assumptions above still govern the number. The worksheet makes the estimate auditable; it does not make it a lender quote, tax return, or personalized advice.